EL-06Electrical

Transformer Sizing Calculator

What to calculate next

Tools commonly used alongside this calculation

Explanation

Sizing a transformer means matching its kVA rating to the load it will serve and then rounding up to the nearest standard size you can actually buy. This calculator takes the load as kVA, as kW with a power factor, or as a secondary current, picks the next standard ANSI/IEEE size, and reports the primary and secondary full-load amps plus the NEC 450.3(B) primary overcurrent device — the numbers you need to specify the unit and its feeder.

How transformer sizing works

Apparent power (kVA) is what a transformer is rated for, so any load given in kW is first converted with its power factor. Full-load amps then follow from the kVA rating and the line-to-line voltage, with a √3 factor for three-phase.

kVA = kW ÷ PF  |  kVA = (1 for 1Ø, √3 for 3Ø) × V × I ÷ 1000
FLA = kVA × 1000 ÷ (V × 1 for 1Ø, V × √3 for 3Ø)
SymbolMeaning
kVAApparent power — the transformer rating
PFPower factor (0–1); about 0.8 for motor-heavy loads
VLine-to-line voltage on the side being calculated
FLAFull-load amps at the rated kVA

Once you know the secondary full-load amps, size the conductors and overcurrent device for that feeder with the wire size & ampacity calculator, then check the run length against the 3% guideline with the voltage drop calculator.

Standard kVA sizes

Transformers are manufactured in fixed steps, so the calculated load is rounded up to the next standard rating. A 40 kW, 0.9 PF load is about 44.4 kVA, which rounds up to a standard 45 kVA three-phase unit. Single-phase and three-phase units use different size ladders.

PhaseCommon standard kVA ratings
5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500
15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500

A common rule of thumb is to load a transformer to no more than about 80% of its rating, leaving roughly 20–25% headroom for future growth and to keep it running cool. Enter that as the spare capacity and the calculator sizes from the adjusted load.

Full-load amps and overcurrent protection

NEC 450.3(B) sets the maximum overcurrent protection for transformers rated 1000 V or less. With protection on the primary side only, the device is sized as a percentage of the primary full-load amps. When 125% does not land on a standard breaker or fuse size, the next higher standard rating is permitted.

Primary currentMax primary OCPD
9 A and over125% (next standard size up permitted)
2 A to under 9 A167%
under 2 A300%

If the installation also has overcurrent protection on the secondary, the primary device may be allowed up to 250% with a corresponding secondary limit. This calculator reports the primary-only case; verify any secondary-protected design against the full Table 450.3(B).

Notes and limitations

This tool sizes a transformer from a single connected load figure. It does not perform a full NEC Article 220 load study — adding up lighting, receptacle, motor, and HVAC loads with their demand factors — so for a service or panel calculation, total the demand load first and enter that result here. Always confirm the final selection, conductor sizes, and overcurrent protection against the current NEC and the authority having jurisdiction.

Frequently asked questions